M.A.S 220-390 (S6B series)

The M.A.S are mounted of a base frame with vibration absorber which eliminates noise resonance, high-frequency vibration and reduces the stress on the foundation. Mitsubishi diesel engine have a generous design margin to drive alternators at 1200, 1500 or 1800 rpm continuously.
 

Gen. Set Model

Engine Model

Continuous Generator Output in KVA
(ISO 3046 / DIN 6271)

1200
1-Min

1500
1-Min

1800
1-Min

M.A.S 220

S6B-MPT

163

226

252

M.A.S 265

S6B-MPTA

177

278

331

M.A.S 290

S6B-MPTK

225

304

358

M.A.S 370

S6B3-MPTA

283

390

450

M.A.S 390

S6B3-MPTK

320

422

492

M.A.S 450

S6A3-MPTA

374

478

552

M.A.S 455

S6R-MPT

374

453

522

M.A.S 500

S6A3-MPTK

380

513

570

M.A.S 525

S6R2-MPT

440

523

-

M.A.S 580

S6R-MPTA

456

611

714

M.A.S 620

S6R-MPTK

504

644

762

M.A.S 675

S6R2-MPTA

576

711

-

M.A.S 730

S6R2-MPTK

595

763

-

M.A.S 765

S12A2-MPTA

654

813

913

M.A.S 775

S12N-MPT

643

775

890

M.A.S 800

S12A2-MPTK

662

849

994

M.A.S 885

S12N-MPTA

797

968

1128

M.A.S 1000

S12N-MPTK

904

1129

1164

M.A.S 1330

S12R-MPTA

912

1331

1428

M.A.S 1345

S12R-MPTK

1008

1355

1524

M.A.S 1560

S16R-MPTA

1224

1580

1908

M.A.S 1650

S16R-MPTK

1334

1710

2028


Remarks: KVA rating at 0.8 pf      Voltage: 50Hz 380/415V • 60Hz 460/480V

Performance based on:
Average load of  continuous rating (100%)   : 60-80%
Annual operating hours                                     : 3000 - 4000
100% load available during 3 hours per 12 hours operating time.

All figure are subject to change without prior notice.
   